OVK
OVK – Which buildings and when?
Below is a table showing the inspection intervals and authorisation levels required for different categories of buildings.
FT-ventilation = mechanical ventilation in which both the extract and supply air flows are controlled by fan.
F-ventilation = mechanical ventilation where the extract air flow is controlled by fan.
S-ventilation = natural ventilation.
FTX-ventilation and FX-ventilation = FT-ventilation and F-ventilation with heat recovery.
N = normal authorisation level.
K = complicated authorisation level.
Buildings | Inspection interval (periodic inspection) | Performance controller's lowest authorisation level |
Pre-schools, schools, health care premises and the like with S, F, FX-ventilation | 3 years | N |
Pre-schools, schools, health care premises and the like with FT, FTX-ventilation | 3 years | K |
Multi-dwelling blocks, office buildings and the like with FT, FTX-ventilation | 3 years | K |
Multi-dwelling blocks, office buildings and the like with F, FX, S-ventilation | 6 years | N |
Single and two-dwelling houses with FX, FT, FTX-ventilation | Control only for new construction and new installation | N |