OVK

OVK – Which buildings and when?

Below is a table showing the inspection intervals and authorisation levels required for different categories of buildings.

FT-ventilation = mechanical ventilation in which both the extract and supply air flows are controlled by fan.

F-ventilation = mechanical ventilation where the extract air flow is controlled by fan.

S-ventilation = natural ventilation.

FTX-ventilation and FX-ventilation = FT-ventilation and F-ventilation with heat recovery.

N = normal authorisation level.

K = complicated authorisation level.

Buildings Inspection interval (periodic inspection) Performance controller's lowest authorisation level
Pre-schools, schools, health care premises and the like with S, F, FX-ventilation 3 years N
Pre-schools, schools, health care premises and the like with FT, FTX-ventilation  3 years K
Multi-dwelling blocks, office buildings and the like with FT, FTX-ventilation 3 years K
Multi-dwelling blocks, office buildings and the like with F, FX, S-ventilation 6 years N
Single and two-dwelling houses with FX, FT, FTX-ventilation Control only for new construction and new installation N